13. When the discharging start wait timer completes the set time;
• The discharging output signal is turned on, and the discharging time monitor timer starts.
14. When the gross becomes lower than the zero range;
• The discharging valve close wait timer starts.
• The discharging time monitor timer is reset.
15. When the discharging valve close wait timer completes the set time, the discharging output signal is turned off.
16. When the Batch Start signal for the next cycle is input;
• The Batch Finish output signal is turned off.
• The judgment result output signal (overlimit or underlimit) is turned off.
• Now, the weighing sequence has cycled and restarts from Step 2 at the same time.